Micropilot FMR67
Endress+Hauser V. 1, Rev. 3, 11-04-2017 11
Galvanic isolation
All circuits for the outputs are galvanically isolated from each other.
Protocol-specific data HART
Manufacturer ID 17 (0x11)
Device type ID 0x112B
HART specification 7.0
Device description files (DTM, DD) Information and files under:
www.endress.com
www.fieldcommgroup.org
HART load min. 250 Ω
HART device variables The measured values can be freely assigned to the device variables.
Measured values for PV (primary variable)
Level linearized
Distance
Electronic temperature
Relative echo amplitude
Area of incoupling
Analog output adv. diagnostics 1
Analog output adv. diagnostics 2
Measured values for SV, TV, FV (second, third and fourth variable)
Level linearized
Distance
Electronic temperature
Terminal voltage
Relative echo amplitude
Absolute echo amplitude
Area of incoupling
Analog output adv. diagnostics 1
Analog output adv. diagnostics 2
Supported functions Burst mode
Additional transmitter status
Wireless HART data
Minimum start-up voltage 16 V
Start-up current 3.6 mA
Start-up time 65 s
Minimum operating voltage 14.0 V
Multidrop current 4.0 mA
Set-up time 15 s