Proline Promass 83 Hardware settings
Endress+Hauser
19
4.2 Device address EtherNet/IP network
Has to be set for measuring devices with the communication method:
• EtherNet/IP
The IP address can be configured via:
• Miniature switches  see description below
• Webserver  see section Software settings, "Device address EtherNet/IP network"
 ä 26
Addressing via miniature switches
#
Warning!
Risk of electric shock! Risk of damaging the electronic components!
• All the safety instructions for the measuring device must be observed and all the warnings
heeded  ä 14.
• Use a workspace, working environment and tools purposely designed for electrostatically
sensitive devices.
A0015112
a. Loosen the cheese head screw of the securing
clamp (1) with an Allen key (3 mm / 0.12 in).
b. Unscrew cover of the electronics compartment (2)
from the transmitter housing.
c. Set the position of the miniature switches (3) on
the I/O board using a sharp pointed object.
Installation is the reverse of the removal procedure.
IP address range: 0 to 254
Default setting: 192.168.212.212 (all miniature switches
= OFF)
A0015114
Example shown:
64+32+1 = IP address 192.168.212.97
Activation hardware addressing:
After 10 seconds the hardware addressing with the defi-
ned IP address is activated.
!
Note!
Deactivation hardware addressing and activation software
addressing ( ä 26):
Switch all the DIP switches for hardware addressing to
OFF.