Output frequency
Switch status
Parameter overview with brief description
Parameter Prerequsite Description User interface
Output current 1 – Displays the current value currently
calculated for the current output.
3.59 to 22.5 mA
Measured current 1 – Displays the current value currently
measured for the current output.
0 to 30 mA
Terminal voltage 1 – Displays the current terminal voltage
that is applied at the current output.
0.0 to 50.0 V
Output current 2 – Displays the current value currently
calculated for the current output.
3.59 to 22.5 mA
Pulse output The Pulse option is selected in the
Operating mode parameter.
Displays the pulse frequency currently
output.
Positive floating-point
number
Output frequency The Frequency option is selected in the
Operating mode parameter.
Displays the value currently measured
for the frequency output.
0 to 1 250 Hz
Switch status The Switch option is selected in the
Operating mode parameter.
Displays the current switch output
status.
• Open
• Closed
11.4 Adapting the measuring device to the process
conditions
The following are available for this purpose:
• Basic settings using the Setup menu
→ 58
• Advanced settings using the Advanced setup submenu → 84
11.5 Performing a totalizer reset
In the Operation submenu the totalizers are reset:
• Control Totalizer
• Reset all totalizers
Function scope of the "Control Totalizer " parameter
Options Description
Totalize The totalizer is started.
Reset + hold The totaling process is stopped and the totalizer is reset to 0.
Preset + hold The totaling process is stopped and the totalizer is set to its defined start value
from the Preset value parameter.
Reset + totalize The totalizer is reset to 0 and the totaling process is restarted.
Preset + totalize The totalizer is set to the defined start value in the Preset value parameterand the
totaling process is restarted.
Hold The totaling process is stopped.