Proline Prosonic Flow B 200 HART Installation
Endress+Hauser 23
6.3 Post-mounting check
Is the device undamaged (visual inspection)?
Does the measuring device conform to the measuring point specifications?
For example:
• Process temperature → 139
• Process pressure (refer to the section on "Pressure-temperature ratings" in the "Technical
Information" document)
• Ambient temperature range → 20
• Measuring range → 130
Has the correct orientation for the sensor been selected → 18?
• According to sensor type
• According to medium temperature
• According to medium properties (outgassing, with entrained solids)
Does the arrow on the sensor match the direction of flow of the medium through the piping
→ 18?
Are the measuring point identification and labeling correct (visual inspection)?
Is the device adequately protected from precipitation and direct sunlight?
Are the securing screw and securing clamp tightened securely?