Proline Prosonic Flow P 500
42 Endress+Hauser
Sensor holder with strapping bands (medium nominal diameters)
Can be used for
Measuring devices with measuring range DN 50 to 4000 (2 to 160")
Mounting on pipes DN ≤ 600 (24")
Procedure:
1. Fit the mounting bolt over strapping band 1.
2. Position strapping band 1 as perpendicular as possible to the measuring pipe axis without
twisting it.
3. Guide the end of strapping band 1 through the strapping band lock.
4. Tighten strapping band 1 as tightly as possible by hand.
5. Set strapping band 1 to the desired position.
6. Push down the tensioning screw and tighten strapping band 1 so it cannot slip.
7. Strapping band 2: proceed as for strapping band 1 (steps 1 to 6).
8. Only slightly tighten strapping band 2 for final mounting. It must be possible to move
strapping band 2 for final alignment.
9. If necessary, shorten both strapping bands and trim the cut edges.
L
WARNING
Risk of injury!
To avoid sharp edges, trim the cut edges after shortening the strapping bands. Wear suitable
gloves and protective goggles.
1
2
3
A0043373
 30 Holder with strapping bands (medium nominal diameters), with hinged screw
1 Mounting bolts
2 Strapping band
3 Tensioning screw
1
2
3
A0044350
 31 Holder with strapping bands (medium nominal diameters), without hinged screw
1 Mounting bolts
2 Strapping band
3 Tensioning screw