RIA45 Commissioning
Endress+Hauser 25
Current Voltage RTD (resistance
thermometer)
TC (thermocouple) Off (Deactivate the
input)
Signal range
Signal range (see Technical data); start and end of measuring
range defined by type selected
Lower range
Start of measuring range; also enter
decimal point
Connection (only
RTD)
Type of connection
(2-, 3-, 4- wire
connection)
Upper range
End of measuring range; also enter
decimal point
TAG
Channel identifier
Unit
Unit
Offset
Constant value that is added to the current measured value
Ref junction (TC
only)
intern / fixed +
entering "Fixed ref
junc" value
Res minmax: (yes/no)
Reset minimum/maximum values?
7.4.3 Step 3: Configuring the calculations
One or two channels with the following functions are available for calculations:
Setup
Calc value 1 Calc value 2
Switched off
Sum (AI1+AI2)
Difference (AI1-AI2)
Average ( (AI1+AI2)/2 )
Linearization AI1
Multiplication (AI1*AI2)
Switched off
Sum (AI1+AI2)
Difference (AI1-AI2)
Average ( (AI1+AI2)/2 )
Linearization AI2
Linearization CV1
Multiplication (AI1*AI2)
TAG
Unit
Bar 0%
Bar 100%
Factor
Offset
To be configured like universal input, see Step 2 →  24
No. lin points → X/Y coordinates
The device has two linearization tables, each with a maximum of 32 linearization points. They are permanently
assigned to the ‘Calc value 1’ and ‘Calc value 2’ channels. If linearization is selected as the calculation, the
number of linearization points needed is specified in the ‘No. lin points’ parameter. An X-coordinate and a Y-
coordinate has to be specified for each linearization point. The linearization tables can be deactivated
individually.
Reset min/max To be configured like universal input, see Step 2 →  24