RIA45 Technical data
Endress+Hauser 49
Accuracy Input: Range: Maximum measured error of
measuring range (oMR):
Typ C (W5Re/W26Re), 0 to 2 320 °C (32 to 4 208 °F)
(ASTME998)
± (0.15% oMR +1.5 K (2.7 °F))
from 500 °C (932 °F)
Typ B (Pt30Rh-Pt6Rh), 0 to 1 820 °C (32 to 3 308 °F)
(IEC60584)
± (0.15% oMR +1.5 K (2.7 °F))
from 600 °C (1 112 °F)
Typ S (Pt10Rh-Pt), –50 to 1 768 °C (–58 to 3 214 °F)
(IEC60584)
± (0.15% oMR +3.5 K (6.3 °F))
für –50 to 100 °C (–58 to 212 °F)
± (0.15% oMR +1.5 K (2.7 °F))
from 100 °C (212 °F)
Typ U (Cu-CuNi), –200 to 600 °C (–328 to 1 112 °F) (DIN
43710)
± (0.15% oMR +1.5 K (2.7 °F))
from 100 °C (212 °F)
AD converter resolution 16 bit
Temperature drift Temperature drift: ≤ 0.01%/K (0.1%/18 °F) oMR
≤ 0.02%/ K (0.2%/18 °F) oMR for Cu100, Cu50, Cu53, Pt50 and Pt46
Analog output:
Current 0/4 to 20 mA, overrange bis 22 mA ±0.05% of measuring range
Max. load 500 Ω
Max. inductivity 10 mH
Max. capacity 10 µF
Max. ripple 10 mVpp at 500 Ω, frequency < 50 kHz
Voltage 0 to 10 V, 2 to 10 V
0 to 5 V, 1 to 5 V
Overrange: up to 11 V, shortcircuit proof, I
max
< 25 mA
±0.05% of measuring range
±0.1 % of measuring range
Max. ripple 10 mVpp at 1 000 Ω, frequency < 50 kHz
Resolution 13 bit
Temperature drift ≤ 0.01%/K (0.1%/18 °F) of measuring range
Galvanic isolation Testing voltage of 500 V towards all other circuits
13.5 Installation
13.5.1 Installation instructions
Mounting location
Panel, cutout 92 x 45 mm (3.62 x 1.77 in) (see 'Mechanical construction').
Max. panel thickness 26 mm (1 in).
Orientation
No restrictions.
The orientation is determined by the readability of the display.
Max. viewing angle range +/- 45° from the central display axis in every direction.