RIA45 Commissioning
Endress+Hauser 33
The damping is specified in seconds (can be configured in steps of 0.1 s, max. 999.9 s).
Default values
Input type Default value
Current and voltage inputs 0.0 s
Temperature inputs 1.0 s
Once 5 times the filter time have elapsed, 99% of the actual measured value is reached.
A0010508
12 Signal damping
Analog In: analog input signal
d: set damping
Failure mode
If an error is detected at one of the two inputs, the internal status of the input is set to
error. The behavior of the measured value in the event of an error can be defined here.
• Invalid = Ungültiger Wert:
The value is not calculated further since it is passed on as an invalid value.
• Fixed value = Konstanter Wert:
A constant value can be entered. This value is used if the device should perform further
calculations. The input continues to be in a fault state. The error flag is also transmitted
if the signal is processed further.
Namur NE43
Only for 4 to 20 mA. The measured value and the cables are monitored in accordance with
NAMUR NE43 recommendations. See → 36 for this purpose. Default value: enabled
Open circ detect
Only for 1 to 5 V. Open circuit monitoring of the input.
Failure delay
Delay time for errors, 0 to 99 s
Allow reset
If this function is activated, the min. and/or max. values can be reset outside the setup in
the Display menu. Active access protection does not lock resetting of this memory.