RMS 621
Endress+Hauser 5
!
Note!
Only one temperature available for liquid heat quantity. A direction signal teriminal is required on
changing flow direction (bi-directional operating mode).
Steam application
Input values: Flow, pressure, temperature 1, (temperature 2)
!
Note!
2 temperature sensors are required for steam diferential applications.
Pressure
Select signal type and terminals and then connect sensor (see example).
Type: Relative- or absolute-pressure? Enter start- and end-values.
Temperature
Select signal type and connect sensor(s) (see example). 2 temperature sensors are required for heat differential measurements.
Application
Application: e.g. Water- heat differential
Operating mode: e.g. heating (this means inflow warm, return cold)
Allocate installation point for flow measurement sensor (warm/cold)
Allocate temperature sensors
Flow
Pulse/PFM (e.g. ProWirl)
Analogue (e.g. Promag) Differential pressure (e.g. Orifice)
Flow
Pulse/PFM (e. g. Prowirl)
Analogue (e. g. Prowirl) Differential pressure (e. g. Orifice)
Flow input Flow input Flow input
Flow meter: Operating volume Flow meter: Operating volume Differential pressure/Orifice.../Gas
Terminals:
– Flow meter with active signal connect to e.g. terminals A10(+)/11(-).
– Flow meter with passive signal select e.g. terminals A10 and connect to terminals A10(-)/82(+).
k factor Start/end value (m
3
/h) Start/end value (mbar)
Pressure
Select signal type and terminals and then connect sensor (see example).
Type: Relative- or absolute-pressure? Enter start- and end-values.
Temperature
Select signal type and connect sensor(s) (see example). 2 temperature sensors are required for heat differential measurements.
Application
Application (1);
Application: e.g. steam mass
Steam type: e.g. superheated
Allocate sensors for flow, pressure and temperature measurement