Soliwave FQR56/FDR56
Installation
14
Endress+Hauser
5�1�2 Notes on orientation
A
B
β
α
4 Orientation
A Detectionrange0.3...100m
B Detectionrange0.03...0.3m
α Angleofradiationapprox.9°
β 90°
•Sincethemicrowavesarepolarised,theFQR56andFDR56mustnotbeoutofalignment
with one another along their longitudinal axis (exception: They may be installed at an angle
of180°relativetooneanotheror90°ifthedetectionrangeisunder300mm,seebelow).
• A minimum distance of 30 mm should be maintained between the FQR56 and the FDR56.
•Ifthedetectionrangeisunder300mm,theFQR56andFDR56shouldbeinstalledatan
angleof90°relativetooneanothertoavoidpossibleoverrangings.