5�1�3 Using reectors
If structural design factors do not allow the FQR56 and FDR56 to be installed directly opposite
oneanother,themicrowavebeamcanberedirectedbymeansofatmetalmirrors(reectors).
α
α
α
α
α
α
1 1 1
6 Usingreflectors
1 Reflector
Please note that the FQR56 and FDR56 must be positioned symmetrically with respect
tothereector(angleofentrance=angleofemission),asotherwisetheFDR56willnot
receive a signal that it can evaluate.
•Usingreectorsreducestherangeofthemicrowavebarrierbyapproximately10%per
reector.
5�1�4 Installation with accessories
Achoiceofdierentprocessadaptersisavailablefromtherangeofaccessories,dependingon
where you want to install the device and on the process conditions.
For more information on the range of available accessories
→51
For more information on the various installation options
→
TI00443F/97/EN
5�1�5 Parallel use
Inpractice,multiplemicrowavebarriersaresometimesusedinparallelatonelocation(e.g.
for detecting multiple level limits in a pipe). To prevent the microwave barriers from inter-
feringwithoneanother,aseparatechannel(between1and5)canbeselectedontheFQR56
transmitterforeachmicrowavebarrier.Additionally,everysecondmicrowavebarriershould
berotatedby90°.