Commissioning
Endress+Hauser 35
Optional: Additional manual calibration with maximum covered path (function 4)
Formostapplicationstheautomaticsetupissucient.Themanualsetupcanbeusedtoadapt
the microwave barrier individually to the application or medium.
Ifaeranautomaticsetuponfreepath(function1)themediumcannotbedetectedsafely
(switchingpointofthelimitdetectionisnotundercutonmaximumcoveredpath),the
sensitivity must be reduced with this manual setup function 4.
Move the encoding switch to position 4
→Displayofthefunctionnumber
Aer2seconds:Displayofthecurrentsignalstrength,example:
Press the or key on the device to achieve an increase or reduction of the signal
strength display with maximum covered path
→Displayofthesignalstrengthwithmaximumcoveredpath(all10LEDsarenotlit)
Move the encoding switch to the initial position 0
→Displayofthecurrentsignalstrength
•TheSoliwavemicrowavebarrieriscalibrated,ifwithmaximumcoveredpath
a) and devices with switching output the switching point (LED 5) is undercut safely or
b) on devices with current output all 10 LEDs are not lit.
• A repeated automatic calibration (function 1 or function 2) resets any calibration carried out
earlier.