Waterpilot FMX21 Commissioning
Endress+Hauser 45
Setup -> Level (LEVEL) menu
The LEVEL menu is only visible if the RIA15 has been ordered with the "Level" option and the display unit is
operated in the HART mode (MODE = HART). The basic settings for the Waterpilot FMX21 level sensor can be
made via the RIA15 with this menu.
RIA15 parameter Corresponds to
parameter of
FMX21
Values
(default=bold)
Visible with Description
P_LRV Empty pressure -1999.9 to 9999.9
Default:
Gauge pressure
sensor: Sensor LRL
Absolute pressure
sensor: 0
Pressure empty calibration using
keys -,+,E
More in-depth description / valid
value range: any value in the range
indicated
1) 3)
Number of decimal places depends
on the configured pressure unit.
P_URV Full pressure -1999.9 ... 9999.9
Default: Sensor URL
Pressure full calibration using keys -,
+,E
More in-depth description / valid
value range: any value in the range
indicated
1) 3)
Number of decimal places depends
on the configured pressure unit.
EMPTY Empty calib. -1999.9 to 9999.9
Default: 0
Level empty calibration using keys -,
+, E
More in-depth description / valid
value range: any value in the range
indicated
1) 3)
Number of decimal places depends
on the configured level unit.
FULL Full calib. -1999.9 ... 9999.9
Default: 100
Level full calibration using keys -,+,
E
More in-depth description / valid
value range: any value in the range
indicated
1) 3)
Number of decimal places depends
on the configured level unit.
LEVEL Level before
linearization
Measured value Displays the measured level
Number of decimal places depends
on the configured level unit.
RESET Enter reset code NO
YES
Reset the FMX21 to factory defaults
1) If the measured value that is read out is too large, it is displayed as "9999.9", for example. To display a valid
measured value, the pressure unit (PUNIT) (or level unit (LUNIT)) must be set to suit the measuring range.
2) Default: depends on the sensor nominal range or as per order specifications
3) The values entered for "Empty calib./Full calib.", "Empty pressure/Full pressure" and "Set LRV/Set URV" must be at
least 1% apart. The value will be rejected, and a message displayed, if the values are too close together. Further