CAN - CANopen Interface
Installation guide
Sub-index 03h: Minimum voltage.
Used with current control and power control.
If HVDC voltage goes below this value, EPC will stop and send an error.
Sub-index 07h: Set current.
If this value is nonzero and control mode (object 6208h) is 1, EPC will set this
current in output 1.
Set current of input 1 and set power of output 1 must be zero to perform
high voltage side current control.
Sub-index 0Eh: Set power.
If this value is nonzero and control mode (object 6208h) is 1, EPC will set this
power in output 1.
Set current of input 1 and set power of output 1 must be zero to perform
high voltage side power control.
Sub-index 0Fh: Maximum charge power.
This object is used in all modes (current control, power control and
autonomous mode).
This value is the maximum value of power when the current is positive
(charging direction).
Sub-index 10h: Maximum discharge power
This object is used in all modes (current control, power control and
autonomous mode).
This value is the maximum value of power when the current is negative
(discharging direction).