EVCO | 06.08.2021 | AZ | 26114CP3OEE104
c-pro 3 OEM - Hardware manual
Menu “Parameters (1)” parameters
N. Param. Def. “Parameters” menu Min/max
19 AI5 NTC Type of probe analog port 5 PTC = PTC probe
NTC = NTC probe
PT1000 = Pt 1000 probe
NTCK2 = Type 2 NTC probe
NTCK3 = Type 3 NTC probe
RESIST = electric resistance reading
20 AI6 NTC Type of probe analog port 6 NTC = NTC probe
PT1000 = Pt 1000 probe
NTCK2 = Type 2 NTC probe
NTCK3 = Type 3 NTC probe
RESIST = electric resistance reading
21
AI7
NTC Type of probe analog port 7 PTC = PTC probe
NTC = NTC probe
0-20mA = Transducer 0-20 mA
4-20mA = Transducer 4-20 mA
0-5V = Transducer 0-5 V ratiometric
0-10V = Transducer 0-10 V
PT1000 = Pt 1000 probe
NTCK2 = Type 2 NTC probe
NTCK3 = Type 3 NTC probe
RESIST = electric resistance reading
22
Al Err Time
2 Analog ports time-out If no communication with an analog port is detected after this span of
time, the controller noties an analog input error
23 AO1 0-10V Type of signal analog port 1 0-10V = 0-10 V
PWM = PWM (Pulse With Modulation)
24 freq 1000 Frequency of the analog port 1 PWM-type
signal
-
25 AO2 0-10V Type of signal analog port 2 0-10V = 0-10 V
PWM = PWM (Pulse With Modulation)
26 freq 1000 Frequency of the analog port 2 PWM-type
signal
-
27 AO3 0-10V Type of signal analog port 3 0-10V = 0-10 V
PWM = PWM (Pulse With Modulation)
28 freq 1000 Frequency of the analog port 3 PWM-type
signal
-
29 AO4 0-10V Type of signal analog port 4 0-10V = 0-10 V
PWM = PWM (Pulse With Modulation)
30 freq 1000 Frequency of the analog port 4 PWM-type
signal
-
Menu “Parameters (2)” parameters
N. Param. Def. “Parameters” menu Min/max
31 I/O
Timeout
60 CANBUS communication time-out to
check the remote I/O values
After this span of time has elapsed with no CANBUS
communication, the controller I/O is disabled
32 En. Prg
Level
NO Access to the level rst page enabled by
pressing a combination of keys
YES = yes
NO = no
33
Password
indi
NO Restriction between the access
passwords of the various levels
NO = It is not necessary to set a password to access the levels below
the one already accessed
YES = it is necessary to set a password to access each level
34
Backlight
TIME Type of backlight OFF = the backlight is never ON
ON = the backlight is always ON
TIME = the backlight stays on for the period of time after the latest key
operation set with the B. Time parameter
35 B. Time 240 Backlight duration Only if the Backlight parameter is set in TIME mode
36 Contrast 20 Display contrast -
37 Date
Char Sep
/ Date separator ASCII character -