EVCO | 06.08.2021 | AZ | 29114CP3OEE104
c-pro 3 OEM - Hardware manual
Menu “Networks” - Submenu “USB” parameters
N. Param. Def. “USB” submenu Min/max
51 USB
Status
Device
- - Reserved
52 Device
Status
Idle
Speed
- - Reserved
Menu “Networks” - Submenu “UART2” parameters
N. Param. Def. “UART2” submenu Min/max
47 Address 1 MODBUS address of the device Signicant only if the communication protocol is of the MODBUS slave
type
48 Baudrate 9600 Baud rate of the MODBUS-type
communication
1200 = 1.200 baud
2400 = 2.400 baud
4800 = 4.800 baud
9600 = 9.600 baud
19200 = 19.200 baud
28800 = 28.800 baud
38400 = 38.400 baud
57600 = 57.600 baud
49 Parity EVEN MODBUS-type communication parity NONE = none
ODD = odd
EVEN = even
50 Stop 1 BIT Number of stop bits of the MODBUS-type
communication
1 BIT = 1 bit
2 BIT = 2 bit
Timeout 0