EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204
page 6 of 86
- 5 analog inputs configurable via configuration parameter for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA / 0-5 V
ratiometric / 0-10 V transducers
- 7 optoisolated digital inputs at 24 VAC / DC
- 3 analog outputs of which 1 non optoisolated PWM output and 2 non optoisolated outputs configurable via configuration
parameter for 0-20 mA / 4-20 mA / 0-10 V signal
- 8 digital outputs (electromechanical relays) of which three 5 res. A @ 250 VAC SPST outputs, four 8 res. A @ 250 VAC SPST
outputs and one 8 res. A @ 250 VAC SPDT output
- 4 non optoisolated communication ports of which 1 CAN port with CANbus communication protocol, 1 RS-485 port with
Modbus slave communication protocol, 1 RS-485 port with Modbus master / slave communication protocol (configurable via
application software) and 1 programming and debugging port
- 1 non optoisolated communication port for gateway c-pro 3 plug-in (available in c-pro 3 NODE mega only).
Through the I / O expansion c-pro 3 EXP hecto or c-pro 3 EXP hecto+ it is possible to increase the number of inputs and outputs.
c-pro 3 EXP hecto is available in blind version and can be used for example with a programmable controller such as c-pro 3 hecto,
c-pro 3 hecto+, c-pro 3 mega or c-pro 3 NODE mega.
The expansion has got:
- 3 analog inputs configurable via configuration parameter for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA / 0-5 V
ratiometric / 0-10 V transducers
- 5 non optoisolated free of voltage digital inputs
- 3 analog outputs of which 1 non optoisolated PWM output and 2 non optoisolated outputs configurable via configuration
parameter for 0-20 mA / 4-20 mA / 0-10 V signal
- 6 digital outputs (electromechanical relays) of which five 5 res. A @ 250 VAC SPST outputs and one 8 res. A @ 250 VAC
SPDT output
- 2 non optoisolated communication ports of which 1 CAN port with CANbus communication protocol and 1 port to update the
firmware of the instrument.
c-pro 3 EXP hecto+ is available in blind version and can be used for example with a programmable controller such as c-pro 3 hecto,
c-pro 3 hecto+, c-pro 3 mega or c-pro 3 NODE mega.
The expansion has got:
- 4 analog inputs of which 3 configurable via configuration parameter for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA /
0-5 V ratiometric / 0-10 V transducers and 1 for NTC probes
- 5 optoisolated digital inputs at 24 VAC / DC
- 3 analog outputs of which 1 non optoisolated PWM output and 2 non optoisolated outputs configurable via configuration
parameter for 0-20 mA / 4-20 mA / 0-10 V signal
- 6 digital outputs (electromechanical relays) of which five 3 res. A @ 250 VAC SPST outputs and one 5 res. A @ 250 VAC
SPDT output
- 2 non optoisolated communication ports of which 1 CAN port with CANbus communication protocol and 1 port to update the
firmware of the instrument.
Through the development environment UNI-PRO 3 (to order separately) it is possible to realize the application software and through the
programming kit EVIF20TUXI (to order separately) it is possible to program the controllers.
The devices look in case 4 DIN modules (c-pro 3 hecto, c-pro 3 hecto+, c-pro 3 EXP hecto and c-pro 3 EXP hecto+), 10 DIN modules
(c-pro 3 mega) or 14 DIN modules (c-pro 3 NODE mega).
Installation is in electrical panel, on DIN rail.
Through the programming key EVKEY 10 (to order separately) it is also possible to make the upload and the download of the
configuration parameters.