Function default
PF
PRE-FLASHING
Enables/disables pre-flashing and specifies when it
is activated. The pre-flashing time is fixed: 3 s.
no disabled
OC for any movement
CL when closing
OP when opening
PA when the pause time elapses
no
Ph
CLOSING PHOTOCELLS
Specifies the operation of the closing photocells.
no reopen immediately
Y reopen when the photocells are released
no
Ad
ADMAP FUNCTION
Enables/disables operation in accordance with
French standard NFP 25/362.
no disabled
Y enabled
no
EC
ANTI-CRUSHING SENSITIVITY
(displayed only if
En = Y)
This function species the speed with which the
anti-crushing system triggers after an obstacle
has been detected.
00…10 (levels, 10 =maximum sensitivity)
06
rB
SEARCH FOR STOP
(displayed only if
En = Y and FA/FC = no
or
2)
This function specifies the angular space in which
to search for the opening/closing stop. In this
space, the automation is stopped by a mechanical
stop/obstacle and not by the anti-crushing system.
Displayed in degrees and tenths of a degree (sepa-
rated by a point) up to 9.9, then it is in degrees.
0.3…9.9 (Adjustment step: 0.1°)
10…20 (Adjustment step: 1°)
4.0
tA
ADDITIONAL OPERATING TIME
(displayed only if
En = no and FA/FC =
no or 2)
Adds additional operating time at the end of the
movement.
00…30 (Adjustment step: 1 s)
03
Function default
o1
OUT1
Function of output OUT1.
00 disabled
01 FAILSAFE
02 LED (lit during OPENING and in OPEN/PAUSE,
off in CLOSED, flashing in CLOSING)
03 timed COURTESY LIGHT
04 ERROR active
05 automation OPEN or PAUSED
06 automation CLOSED
07 automation MOVING
08 automation IN EMERGENCY
09 automation OPENING
10 automation CLOSING
11 electric lock OPERATION
12 PHOTOCELL active
13 TRAFFIC LIGHT function (active during
OPENING and with automation OPEN)
14 timed output that can be activated from the
2
nd
radio channel OMNIDEC
15 output (step-by-step function) that can
be activated from the 2
nd
radio channel
OMNIDEC
16 active during the movement of MOTOR 1
17 active during the movement of MOTOR 2
18 INTRUSION alarm (only with encoder
installed)
00
t1
OUT1 TIMING
(displayed only if
o1 = 03/11/14)
Sets the activation duration of output OUT1 if a
timed function is programmed.
01…30 (Adjustment step: 1 min if
o1 = 03/14 , 1 s if o1 = 11)
02
o2
OUT2
Function of output OUT2 (with the same options
as
o1).
02
t2
OUT2 TIMING
Timing of output OUT2 (with the same options
as
t1).
02
AS
MAINTENANCE REQUEST
Enables/disables the maintenance alert when the
programmed number of cycles has been reached
as specified in the following functions (
nc, nd).
no disabled
Y enabled
no