Chapter 6 Description of Operations
PAGE 6-51
D-No. 500 IP Address (upper 6 digits) D-No. 501 IP Address (lower 6 digits)
Setting range: 0 ~ 255
The IP address of the touch panel connected in the controller is indicated.
D-No.502 Touch Panel Function / Language Setup standard setting : 0 Setting range : 0~4
Disabling/enabling of the touch panel function and the language setting are changed.
●If the touch panel is not used
Set ”0.”
●If the touch panel is used
Set any of “1” ~ “4” in accordance with the language to be used.
Touch Panel Function Disable
D-No.503 Port Number standard setting : 1024 Setting range : 1024~65535
The Port Number of the touch panel connected in the controller is indicated.
・ After being changed, the settings of D-Nos. 500 ~ 503 are made available by
reactivation of the control power.
・Please execute the reactivation of the control power after confirming that the “Prog”
indication on the upper stage of the indicator changes from being lit up
to being unlit after changing the setting.
・If the control power is turned OFF while “Prog” lights up, the parameters may become
initialized.