3.3.7 Error reaction (fail-state settings)
The reaction of the bus node to the followi ng errors is de-
pendent on the parameterised fail-safe setting and the (con-
figured) reaction of the controller, i.e. the PLC, the IPC or the
application program:
(Master) controller stops
Network interruption
Telegram failure
Depending on the parameterisation, the outputs (valves and
electrical outputs) wil l be:
switched off (output signal reset, in the case of analogue
outputs to 0; factory setting)
switched on (output signal set, in the case of analogue
outputs to the parameterised value)
kept in the same state (“freezi ng” of output signal)
You can define two types of error reaction for the controller
(or the application program):
Hard error reaction:
The controller switches to STOP”/PRE-OPERATIONAL
mode when a fault occurs
Soft error reaction:
The controller remains in “RUN”/SAFE-OPERATIONAL (or,
if relevant, OPERATIONAL) mode when a fault occurs