Twinflex V3 Control Panel Engineering and Commissioning Manual
25
Access Level 1 (Normal)
In the ‘Normal’ state the panel is active in detecting fire and fault conditions and will sound the alarm
sounders when it is triggered. The ‘User Controls’ are disabled and a code entry is required for any
operation of the system.
The only indication at this point should be the green ‘POWER’ light, unless any fire or fault conditions are
detected.
To Enter Access Level 2 ‘User’ mode (2 or 4 zone panels)
1. Press ACCESS’ and then 514 The buzzer will be heard on each key press, and
when successfully entered the ‘CONTROLS
ENABLED’ light will light up continuously.
If an incorrect code is entered, simply start the
above sequence again.
To Enter Access Level 2 ‘User’ mode (8 zone panels)
1. Insert the key and turn
clockwise
The ‘CONTROLS ENABLED’ light will light up
continuously.
Access Level 2 (User)
In the ‘User’ state the panel is still active in detecting fire and fault conditions and will sound the alarm
sounders when it is triggered. The ‘User Controls’ are enabled and operate as described below.
At this point the control panel indication should include a steady green ‘POWER’ light and a steady yellow
‘Controls Enabled’ light, unless any fire or fault conditions are detected.
The control panel will time out of this mode in approximately 5 minutes from the last key press, returning to
Access Level 1 (Normal).
To Exit Access Level 2 ‘User’ mode (2 or 4 zone panels)
1. Press ACCESS’ and then 514 A continuous buzzer tone will start when ‘ACCESS’
is pressed, and will continue until the code is
finished. When complete the ‘CONTROLS
ENABLED’ light will turn off.
If an incorrect code is entered, press the ‘ACCESS’
button before starting the above sequence again
To Exit Access Level 2 ‘User’ mode (8 zone panels)
1. Turn the key anti clockwise and
remove it.
The ‘CONTROLS ENABLED’ light will turn off.