Twinflex V3 Control Panel Engineering and Commissioning Manual
37
We also recommend that all devices, which are set to ‘heat only’, are tested for smoke operation, to ensure
that the smoke detection has been correctly disabled.
Due to the complexity and inherent importance of a life protection type system, training on this equipment
is essential, and commissioning should only be carried out by competent persons.
End User Training
A Fire Alarm System is of little use if the end user and/or the responsible persons who will be present in
the building do not know how to operate and respond to the system. It is therefore essential that
commissioning includes training for the users of the system and responsible persons.
User instructions and a Zone Chart should be left adjacent to the control panel. As access to the system
must be controlled by responsible persons, it would be unusual to display the access codes on this notice.
These codes must however be available for the responsible persons, so ensure that they know and record
them in a secure place.
The Twinflex User Guide should be explained and left with the responsible person on site, for storage in an
accessible and known location, in order that the responsible person and the service engineer may keep
information records up to date.
A single page user instruction sheet is included at the end of this manual. A copy of this should be
mounted adjacent to the control panel.