ESC and ENTER keys
Table 40: ESC and ENTER key function in SW zone
Key Function
ESC Use to delete the procedure
and return to the programming
screen
ENTER Use to accept the selection and
activate the corresponding
programming screen
Figure 28: Selecting and programming SW zone
Callout Description
1 Index of SW zone program
2 Access level
3 Control panel status
4 If blinking, the control panel is
working properly
5 Name of control panel
6 Select between ON or OFF
Sounders on (3s)
If YES, every test event (input activation) activates
the sounders in the same zone for 3 seconds.
SMOKE DELAY (60s/30min)
For each zone, program the delayed activation
of smoke detectors according to the following
schedule:
If the smoke level exceeds the alarm threshold,
the panel does not signal anything at first. After
60 seconds, if the smoke level is still above the
threshold, the system goes into alarm condition.
Otherwise, there are no signals. If a new alarm
from the same detector or the activation of another
sensor in the same zone occurs within 30 minutes,
the alarm of fire panel triggers.
In this phase, the keypad and keys have the
following functions:
Alphanumeric keypad
No function is related to the alphanumeric keypad.
Cursor keys
Table 41: Cursor key functions in smoke delay
Key Function
Up No function
Down No function
Right Use to select ON-OFF
Left Use to select ON-OFF
ESC and ENTER keys
Table 42: ESC and ENTER key function in smoke
delay
Key Function
ESC Use to delete the operation and
return to the previous screen
ENTER Use to accept the selection and
activate the programming screen
Delay To Alarm
For each zone, you can program the activation of
a common delay to alarm delay of 9 minutes. The
procedure and the functionality of the cursors, ESC,
and ENTER keys are the same as the SMOKE DELAY
parameters. See Figure 29, d.
FC503 and FC506 Addressable Fire Control Panels 53