Figure 31: Selecting and programming SC active
on disablement options
Callout Description
1 Control panel name
2 Output number
3 Access level
4 Control panel status
5 If blinking, the control panel is
working properly
6 Output type
7 Output number
8 Insert output label
9 Select ON or OFF
Output Name
Enter or modify the relevant output name using the
alphanumeric keypad. The maximum number of
characters is twenty.
Trigger Zone 1
Select the first zone for which events, defined later,
the output will become active. The entry 0000 means
No Zone. Numeric entry modes range from 0 to 128
for FC503 and 0 to 256 for FC506.
Trigger Zone 2
Select the second zone for which events, defined
later, the output will become active. The entry 0000
means No Zone. Numeric entry modes range from 0
to 128 for FC503 and 0 to 256 for FC506.
Trigger Event
Define, for both trigger zones, the event types valid
to activate the relevant output. The event type codes
are shown in Table 45.
Table 45: Trigger Event Codes
Code Event Type
ala Alarm
dly Delay to Alarm
war Warning
fau Fault
tst Test
dk Double Knock
You can select more than one trigger event using
the multiple selection mode. The selected events are
valid for all trigger zones.
When zones trigger condition act in OR mode, it is
sufficient that the trigger condition of a single zone
is matched to activate the output.
Silenceable
Use SILENCEABLE to select if the output stays active
until the SILENCE/RESOUND SOUNDERS key is
pressed (on option set) or stays active until the
RESET key is pressed (off option set).
When a SILENCEABLE output is silenced, you may
reactivate it by pressing the SILENCE/RESOUND
SOUNDERS key again.
Monostable
Set MONOSTABLE to ON to automatically deactivate
the relevant output when the MONOST. OUTPUT
TIME elapses.
The MONOST. OUTPUT TIME is set in the SYSTEM
section of the PROGRAM menu and its value is valid
for all outputs.
Key- network
About this task:
The network option of the programming menu
activates the procedure to configure the FC500MFI
modules.
Complete the following steps when all the control
panels and the FC500MFI modules are connected in
the network:
1. Use the 5 Key to select network from the
Programming screen in the user interface. See
Figure 24, 0.
FC503 and FC506 Addressable Fire Control Panels56