Note: If the enrolling result differs from the
previously stored loop configuration a warning
message displays and it is possible to reject
the present enrolling result, maintaining the
previous configuration, or accept them. See
Figure 26, 1A.
Auto-addressing
About this task:
The second phase of auto-addressing starts if any
devices have been identified as not addressed
during the auto-learning phase or have an address
greater than 250. During this phase, all the not
addressed devices are detected. The panel assigns
them a temporary address and configures them at
default.
See Figure 26, 2A.
If you stop the AUTO option at the end of the
second phase, the following results occur:
• The auto assignment of the address to the not
addressed devices
• The control panel takes over all devices
• The programming devices to their default
configuration.
• Automatic assignment of labels.
• Automatic assignment of zones based on a
loop of belonging.
• The output channels of the modules,
sounders and beacons is set to active on the
alarm of the assigned zone. See Figure 26, B.
3 Device mapping
The third and last phase activates on demand at the
end of the auto-addressing phase.
In this phase, the following options are possible:
• Locate the positioning in the system of all the
devices through their activation.
• In the case of output modules only, sounders
or beacons, the devices are suitably activated
by the panel (see Figure 26, 3A).
• Carry out a preliminary test of the system.
• Program the most important parameters of
each located device.
• Automatically assign labels to all devices.
• Automatically assign the zones based on the
assigned addresses of the devices.
• Automatically configure the output channels
of the modules, sounders, and beacons to
activate on the alarm of the assigned zone.
Table 59: Messages and required actions during the enroll process in function of the loop and panel
configuration.
MESSAGE
LOOP PANEL Differences found!
Automatic zones
assignment
Not addressed
devices found
Start auto-
addressing
1 All devices not
addressed
DEFAULT *
2 Some devices
addressed
+
Some devices not
addressed
DEFAULT (Applicable only to
already addressed
devices)
*
*
3 All devices
addressed
DEFAULT *
4 Fully addressed
Same configuration
CONFIGURED
FC503 and FC506 Addressable Fire Control Panels 67
Johnson Controls - CONFIDENTIAL