Note: If the enrolling result differs from the
previously stored loop configuration a warning
message displays and it is possible to reject
the present enrolling result, maintaining the
previous configuration, or accept them. See
Figure 26, 1A.
Auto-addressing
About this task:
The second phase of auto-addressing starts if any
devices have been identified as not addressed
during the auto-learning phase or have an address
greater than 250. During this phase, all the not
addressed devices are detected. The panel assigns
them a temporary address and configures them at
default.
See Figure 26, 2A.
If you stop the AUTO option at the end of the
second phase, the following results occur:
The auto assignment of the address to the not
addressed devices
The control panel takes over all devices
The programming devices to their default
configuration.
Automatic assignment of labels.
Automatic assignment of zones based on a
loop of belonging.
The output channels of the modules,
sounders and beacons is set to active on the
alarm of the assigned zone. See Figure 26, B.
3 Device mapping
The third and last phase activates on demand at the
end of the auto-addressing phase.
In this phase, the following options are possible:
Locate the positioning in the system of all the
devices through their activation.
In the case of output modules only, sounders
or beacons, the devices are suitably activated
by the panel (see Figure 26, 3A).
Carry out a preliminary test of the system.
Program the most important parameters of
each located device.
Automatically assign labels to all devices.
Automatically assign the zones based on the
assigned addresses of the devices.
Automatically configure the output channels
of the modules, sounders, and beacons to
activate on the alarm of the assigned zone.
Table 59: Messages and required actions during the enroll process in function of the loop and panel
configuration.
MESSAGE
LOOP PANEL Differences found!
Automatic zones
assignment
Not addressed
devices found
Start auto-
addressing
1 All devices not
addressed
DEFAULT *
2 Some devices
addressed
+
Some devices not
addressed
DEFAULT (Applicable only to
already addressed
devices)
*
*
3 All devices
addressed
DEFAULT *
4 Fully addressed
Same configuration
CONFIGURED
FC503 and FC506 Addressable Fire Control Panels 67