Note: You can launch the procedure for the
device mapping outside the AUTO function
by activating the localization programming
function (key 6 on the PROGRAM status).
Localization activates the procedure for devices
mapping on demand, on a system already
configured, and without the need to proceed to
their activation. It is meant to correct errors or
change the system on the run and use all the
features and capabilities described above.
System default
• Zone assignment
To mimic a conventional panel, the acquired
device over the loops are automatically assigned
to a predefined zone. The two scenarios for zone
assignment are:
1. If you exit at the end of the Auto addressing
phase without executing the Device Mapping
process, the zone assignments are:
1. Zone 1: all the devices located on Loop 1
(sub loop 1)
Zone 2: all the devices located on Loop 2
(sub loop 2)
Zone 3: all the devices located on Loop 3
(sub loop 3)
2. If you execute the Device Mapping process,
the device address to zone assignments at the
end of the process are:
For Main Loop 1
The first two addresses are assigned to zone 1
The next two addresses are assigned to zone 2
:
:
The last addresses (249 and 250) are assigned to
zone 125
For Main Loop 2
The first two addresses are assigned to zone 129
The next two addresses are assigned to zone 130
:
:
The last addresses (249 and 250) are assigned to
zone 253
Note: For Main Loop 1 of FC503, do not assign
devices to zones 126, 127, and 128.
For Main Loop 1 and Main Loop 2 of FC506, do
not assign devices to zones 126, 127, 128, 254,
255, and 256.
If an address is not manually assigned to a device,
either through the FC490ST or during the device
mapping phase, no zone is assigned to it.
The previous zone assignment schemes are also
applied to the first trigger zone in the case of output
only devices such as sounders, beacons, and SNM
modules or output channel of the input output
devices.
Note: In the case of non-zone assigned, the
output channel trigger event is the panel
alarm.
System default parameters
Temperature Detector Default values
Label See note 1 (**)
Enablement Enabled
LED blink On
Assigned zone (see: "Zone
assignment)
Base type Normal
Use zone setting Yes
Day operating mode A2S
Night operating mode A2S
Smoke Detector Default values
Label See note 1 (**)
Enablement Enabled
LED blink On
Assigned zone (see: "Zone
assignment)
Base type Normal
Use zone setting Yes
Day smoke sensitivity Medium
Night smoke sensitivity Medium
Smoke + Temperature
Detector Default values
Label See note 1 (**)
Enablement Enabled
LED blink On
FC503 and FC506 Addressable Fire Control Panels 69