Specifications
The information in this section is aimed at suitably
qualified technicians experienced in the installation
and commissioning of fire detection and alarm
systems, who have also received FIRECLASS training.
Technical features
Table 61: FC503 and FC506 technical features
Control panel FC503 FC506
230 V~ 230 V~Main voltage
60/50 Hz -15/+10%
Aux. outputs nominal
voltage
27.6V
Aux. outputs min. and max.
voltage
19.0 ÷ 27.6V
Minimum output voltage 19.0 VDC ± 5 %
Maximum current drawn 1.6 A (230V)
Ripple 1 %
Maximum internal
resistance of the battery and
associated circuitry
1 ohm
Temperature range -5°C to +40°C
Storage temperature -20°C to +70°C
Operating humidity Up to 95% non-
condensing
Dimensions (W x H x D) 429.62 mm x 493.17
mm x 126.97 mm
Table 61: FC503 and FC506 technical features
Control panel FC503 FC506
Weight (Without batteries) 8 kg
Table 62: FC500 technical features
Repeater FC500
Operating voltage 27.6 VDC
Maximum current 130 mA
Temperature range -5 to +40°
Storage temperature -20°C to +70°C
Operating humidity Up to 95% non-
condensing
Dimensions
(W x H x D)
345.44 mm x 234.61
mm x 55.72 mm
Weight 2.7 kg
Description of the terminals
Table 63 describes the terminals of the main board
and switching power.
The first status is the standby (normal) status,
followed by the alarm status. The voltage present
during the different operating conditions is
indicated for each terminal, as well as the maximum
current in amps that can circulate.
Table 63: Terminals description
TERM. Description v(V) i(A)
Main boards
+L1- LEFT (+)Loop 1-Positive signal, left side.
(-)Loop 1-Negative signal (return), left side
+L1- RIGHT (+)Loop 1-Positive signal, right side.
(-)Loop 1-Negative signal (return), right side
+L2- LEFT (+)Loop 2-Positive signal, left side.
(-)Loop 2-Negative signal (return), left side.
+L2- RIGHT (+)Loop 2-Positive signal, right side.
(-)Loop 2-Negative signal (return), right side.
+L3- LEFT (+)Loop 3-Positive signal, left side.
(-)Loop 3-Negative signal (return), left side.
FC503 and FC506 Addressable Fire Control Panels 83