Table 59: Messages and required actions during the enroll process in function of the loop and panel
configuration.
MESSAGE
LOOP PANEL Differences found!
Automatic zones
assignment
Not addressed
devices found
Start auto-
addressing
New configuration (Applicable only
to all already
addressed devices)
*
5 Fully addressed
Different
configuration
CONFIGURED
*
Add devices (Applicable only
to new already
addressed devices)
*
6 Same configuration
+
Not addressed
devices
CONFIGURED *
New configuration (Applicable only
to all already
addressed devices)
*
*7
1
Different
configuration
1
+
Not addressed
devices
CONFIGURED
*
Add devices (Applicable only to
the new already
addressed devices)
*
*
1 Note: (*) indicates that the message is displayed and relevant action is executed.
The third phase represents a powerful and flexible
tool that allows you to draw the plant being in front
of the panel and without the use of a PC and its SW
configuration.
A series of controls have been designed to prevent
the generation of incorrect or unmanageable
conditions.
Assign each device an address. Ensure that the
address meets the following conditions:
The address does not belong to an older
generation device from the FC400 series.
For FC503: The address is in the range of 1 to
250.
For FC506: The address for the first loop is in
the range of 1 to 250 and the address for the
second loop is in the range of 1 to 250.
The address belongs to a new generation
device and the device is present in the list of
located devices.
The address is not a duplicate of an
automatically assigned address.
In each case at the end of the device mapping
phase a check is performed to detect the presence
of doubles addresses. See Figure 26, C. In this
case the involved addresses are indicated and it is
not possible to end the procedure until the error
condition is removed.
FC503 and FC506 Addressable Fire Control Panels68
Johnson Controls - CONFIDENTIAL