Table 63: Terminals description
TERM. Description v(V) i(A)
Main boards
+BAT- BATTERY CONTROL PANEL POWER SUPPLY 27.6
[OC1] [OC2] Programmable Outputs(Open collector)- Silenceable-Bypassable
(Disabled)-Supervised
(The polarity is not programmable)
27.6
[SC1]
[SC2]
(Programmable, SC2 only),Supervised, Silenceable, Bypassable
(Disabled) ALARM Outputs: Panel in Standby negative on [+]
terminal; positive 27.6 V on [–] terminal
Panel in Alarm positive 27.6 V on [+] terminal; negative 0 V on [–]
terminal
(2)
Table 64: Current distribution of FC506 control
panel
FC506 control panel
Switching power supply BAQ140T24 (Imax = 5.5 A)
IBattery_Charge_80%_24H =
(12*0.8)/24 = 400 mA
IFor_panel = 5500 - 400 = 5100 mA
Panel load distribution
IMain_Board_Electronics = 250 mA
ITotal_Loops_1_2_3 (*) = 800 mA
@40V (1300 mA @27V)
ITotal_Loops_4_5_6 (**) = 800 mA
@40V (1300 mA @27V)
ITotal_Outputs (***) = 2000 mA
IFC500IP = 100 mA (****)
12 Ah
Battery
IResidual = 150 mA
IBattery_Charge_80%_24H =
(17*0.8)/24 = 566.66 mA -> 600 mA
IFor_panel = 5500 - 600 = 4900 mA
Panel load distribution
IMain_Board_Electronics = 250 mA
ITotal_Loops_1_2_3 (*) = 800 mA
@40V (1300 mA @27V)
ITotal_Loops_4_5_6 (**) = 800 mA
@40V (1300 mA @27V)
ITotal_Outputs (***) = 1900 mA
IFC500IP = 100 mA (****)
17 Ah
Battery
IResidual = 50 mA
Table 64: Current distribution of FC506 control
panel
FC506 control panel
IBattery_Charge_80%_24H =
(38*0.8)/24 = 1266.66 mA -> 1500 mA
IFor_panel = 5500 - 1500 = 4000 mA
Panel load distribution
IMain_Board_Electronics = 250 mA
ITotal_Loops_1_2_3 (*) = 800 mA
@40V (1300 mA @27V)
ITotal_Loops_4_5_6 (**) = 800 mA
@40V (1300 mA @27V)
ITotal_Outputs (***) = 1000 mA
IFC500IP = 100 mA (****)
38 Ah
Battery
IResidual = 50 mA
Note:
(*): ITotal_Loops_1_2_3 is the sum of
currents absorbed on Loops 1, 2, 3
(**): ITotal_Loops_4_5_6 is the sum of
currents absorbed on Loops 4, 5, 6
(***): ITotal_Outputs is the sum of the
currents drawn by the terminals SC1, SC2,
24A, 24R, 24V-RS485.
(****): If the FC500IP module is not be
used then the relative amount of current
(100 mA) can be drawn from the SC1,
SC2, 24A, 24R, 24V-RS485 terminals.
FC503 and FC506 Addressable Fire Control Panels 85
Johnson Controls - CONFIDENTIAL