EasyManua.ls Logo

FIRETRACE FK-5-1-12 - Discharge Piping and Fitting Specifications; Maximum Discharge Piping and Fitting Limitations; Table 33 - Discharge Piping Specifications; Table 34 - Flexible Discharge Hose Specifications

FIRETRACE FK-5-1-12
102 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
800027-A 27 06/05/2023
4.7.3 Discharge Piping and Fitting Specifications
All Firetrace ILP Units shall use copper tubing or equivalent, or the Firetrace discharge hoses for the FK-5-1-12 distribution system. The following
tubing and fittings shall be used. Refer to NFPA 2001, 2015 Edition - Section 4.2 for alternate discharge network options.
Table 33 Discharge Piping Specifications
Unit Assembly
Material
Outer Diameter
Wall Thickness
940205
soft annealed copper
(AS B-280
*
, for air conditioning and
refrigeration service)
5/16 in
.032 in
940555
1/2 in
.032 in
941055
1/2 in
.032 in
942055
1/2 in
.032 in
*
The use of AS B-280 soft annealed copper, as specified in this manual, complies with ASME B 31.1 requirements of
NFPA 2001.
Table 34 Flexible Discharge Hose Specifications
Flexible Hose Part
Number
Description
201820
1/2 in Flexible Hose, 2 ft
201821
1/2 in Flexible Hose, 4 ft
201822
1/2 in Flexible Hose, 6 ft
201823
1/2 in Flexible Hose, 8 ft
201824
1/2 in Flexible Hose, 10 ft
Table 35 Discharge Pipe Fitting Specifications
Material
Connection
Type
Minimum Pressure Rating
**
Brass
Flareless Bite
*
1000 psig
*
Use Parker Intru-Lok, Camozzi, or equivalent
**
Minimum pressure rating for use with Firetrace FK-5-1-12 ILP Units
4.7.4 Maximum Discharge Piping and Fitting Limitations
Table 36 Discharge Piping Limitations, the below table shows the discharge piping and pipe fitting limitations for Firetrace Pre-Engineered FK-5-1-
12 ILP Automatic Suppression Units.

Table of Contents