800027-A 47 06/05/2023
Table 56 Class A Fire Enclosure Volume Limitations for 941055 Unit Assembly
Design Temperature
Maximum Enclosure Volume
Concentration
°F
°C
ft³
%
0
-17.8
201.0
5.69
4.675
10
-12.2
205.9
5.83
20
-6.7
210.9
5.97
30
-1.1
215.9
6.11
40
4.4
220.9
6.25
50
10.0
225.9
6.40
60
15.5
230.8
6.54
70
21.1
235.8
6.68
80
26.7
240.8
6.82
90
32.2
245.8
6.96
100
37.8
250.7
7.10
110
43.3
255.7
7.24
120
48.9
260.7
7.38
130
54.4
265.7
7.52
Table 57 Class A Fire Enclosure Volume Limitations for 942055 Unit Assembly
Design Temperature
Maximum Enclosure Volume
Concentration
°F
°C
ft³
%
0
-17.8
401.9
11.38
4.675
10
-12.2
411.9
11.66
20
-6.7
421.8
11.95
30
-1.1
431.8
12.23
40
4.4
441.8
12.51
50
10.0
451.7
12.79
60
15.5
461.7
13.07
70
21.1
471.6
13.35
80
26.7
481.6
13.64
90
32.2
491.5
13.92
100
37.8
501.5
14.20
110
43.3
511.4
14.48
120
48.9
521.4
14.76
130
54.4
531.3
15.05
Class B Fires (All FK-5-1-12 agents)