4.8 Firetrace Detection/Actuation Tubing
The location of the Firetrace detection tubing is critical to the response time in the event of a fire. The Firetrace detection tubing should be installed
throughout the enclosure and routed in close proximity to all potential fire sources. The Firetrace detection tubing should not be placed horizontally
adjacent to a potential fire source.
Table 38 Firetrace Detection Tubing Limitations
Description
Limitation
Maximum length
120 ft
36.58 m
Maximum height between layers
3.28 ft
1 m
Maximum distance between passes
21.12 in
53.8 cm
Maximum distance from wall
10.56 in
26.82 cm
Minimum bend radius
6 in
15.24 cm
Side View Top View
Figure 16 Tubing Configuration Guideline (Side View and Top View)