Manual Flamcomat MK-U G4
We reserve the right to change designs and technical specifications of our products.
28
ENG
7.5 Malfunction messages
Procedures and values for error identification, evaluation and output have been tried in practice, prevent secondary failures
and invite user awareness. Please note that incorrect set-up conditions can lead to repeated errors and inhibit the intended
use. Examples of incorrect set-up conditions are: incorrect or no longer applicable design, outdated equipment, incorrect
installation and inadmissible operational parameters
Error #
GUI Action
0
Single compressor maximum run time error Compressor failure. Check functioning of compressor. Call Technical support if
no solution can be found.
1
Redundant compressors maximum run time error Compressor failure. Check functioning of compressor. Call Technical support if
no solution can be found.
2
Load dependant compressors maximum run time error Compressor failure. Check functioning of compressor. Call Technical support if
no solution can be found.
3
Single compressor current error Potential failure of compressor. Check electrical connection of compressor. Call
Technical support if no solution can be found.
4
Compressor A current error (double compressor configuration) Potential failure of compressor. Check electrical connection of compressor. Call
Technical support if no solution can be found.
5
Compressor B current error (double compressor configuration) Potential failure of compressor. Check electrical connection of compressor. Call
Technical support if no solution can be found.
6
Compressors A and B current error (double compressor
configuration)
Potential failure of compressor. Check electrical connection of compressor. Call
Technical support if no solution can be found.
7
Compressor C current error Potential failure of compressor. Check electrical connection of compressor. Call
Technical support if no solution can be found.
8
Self-learning valve correction error Please reset the error by acknowledging the error in current error/warnings
9
Self-learning compressor correction error Please reset the error by acknowledging the error in current error/warnings
10
Pressure sensor current exceeded Check if the cable to the pressure sensor is not damaged
11
Pressure sensor no current Check if the cable to the pressure sensor is connected
12
Load cell current exceeded Check if the cable to the level sensor is not damaged
13
Load cell no current Check if the cable to the level sensor is connected
14
Compressor A power consumption too high Potential failure of compressor. Check electrical connection of compressor. Call
Technical support if no solution can be found.
15
Compressor B power consumption too high Potential failure of compressor. Check electrical connection of compressor. Call
Technical support if no solution can be found
16
Compressor C power consumption too high Potential failure of compressor. Check electrical connection of compressor. Call
Technical support if no solution can be found
17
Maximum run time M1 exceeded The compressor runs too long. Please make sure there is no leakage in the
system
18
Maximum run time M2 exceeded The compressor runs too long. Please make sure there is no leakage in the
system
19
Maximum suppletion threaded water amount exceeded Please replace a filter
20
Compressor running, no decrease of water level in vessel Potential failure of compressor(s) or clogged tube
21
Valve open, no increase of water level in vessel Potential failure of valve(s) or clogged tube
26
System run in auto mode You have le the manual mode. Automat maintains the pressure
29
Manual mode active, press V to start automat Acknowledge this message to run the automat in the AUTO mode (to leave the
MANUAL mode)
30
Diaphragm rupture The membrane is ruptured and should be replaced