Argus E25 MOD II - Operating Instructions
32
ATTENTION!
When setting the end-position
limit switches, it is necessary to
dismantle the unit, including the
valve. To dismantle the valve,
please see the separate operat-
ing instructions.
Changing the limit switch plate
When a limit switch plate, or one of its
elements is defective, the entire sub-
assembly must be replaced.
The same procedure for replacing the
limit switch plate applies for all operat-
ing voltages and all types of power
supply.
DANGER
When working on pipelines, very
serious injuries or death can be
caused by burns, high pressure
in the system, or poisoning.
Make sure there are no hot
or hazardous media on the
unit or in the pipelines.
Make sure the unit is dis-
connected from all electric
power supplies.
Make sure the plant is
switched off and secured
against unauthorised
switching back on.
Make sure the unit and
valve, including pipelines,
have cooled so that they are
no more than hand warm.
Wear suitable protective
clothing and, when neces-
sary use suitable protective
equipment.
For more information about suitable
protective clothing and protective
equipment, see the safety data sheet
for the medium being handled.