Page 55
FW-E115-P-M_v0203_03_EN.docx
Historical previous day totals of the E115-P – Integer based – Contiguous read
The read-out of historical previous day totals is done via 2 INDEXED variables containing the number of decimals and the value.
These 2 variables can be read as one contiguous list of 3 registers (in a single read action).
Reading is done by first selecting the right entry (day) through the index. Valid values for the index are 0…14, which correspond with
the previous day totals of 1 day old through 15 days old. Indexes outside this range will result in an error being sent back.
(See the communication-section of this appendix for setting the index and its extended functionality through variable 150 and 149).
Previous day total
decimals
0.000…9999999999
Representation: unit depends on variable 32,
decimals depends on variables 5888 (0x1700)
Runtime variables of the E115-P – Integer based – Contiguous read
See list at register 516 in ‘individual read’ section.
grand total
(differential)
0.000…9999999999
Representation: unit, decimals depending on
variables 32, 33
grand accumulated
total (differential)
0.000…99999999999999
Representation: unit, decimals depending on
variables 32, 33
grand flow rate
(differential)
0.000…9999999
Representation: unit, time, decimals depending
on variables 48, 49, 50
0.000…9999999999
Representation: unit, decimals depending on
variables 32, 33
0.000…9999999999
Representation: unit, decimals depending on
variables 32, 33
0.000…9999999999
Representation: unit, decimals depending on
variables 32, 33
accumulated total A
(forward)
0.000…99999999999999
Representation: unit, decimals depending on
variables 32, 33
0.000…9999999
Representation: unit, time, decimals depending
on variables 48, 49, 50
0.000…9999999999
Representation: unit, decimals depending on
variables 32, 33
accumulated total B
(reverse)
0.000…99999999999999
Representation: unit, decimals depending on
variables 32, 33
0.000…9999999
Representation: unit, time, decimals depending
on variables 48, 49, 50
Note: The list of runtime variables shown above can be read as one contiguous list of registers. Unused registers return 0.