Insulation Tester
The Tester
13
Surface Leakage
Current
Shield
( )
( )
GHH13.EPS
Figure 6. Surface Leakage Current
Figure 7 shows how to prevent surface current leakage with a lead connected
from the Guard terminal to a conductor that surrounds the inner insulation. The
surface leakage current is directed to the Guard terminal. This removes the
leakage current from the measurement path between the positive and negative
terminals, and improves the accuracy of the test readings.
Leakage
Current
G
Shield
( )
( )
( )
Optional
GHH14.EPS
Figure 7. Guard Terminal Connection
Figure 8 shows how make the measurement setup better. Connect the Guard
terminal to the unused wire and attach it to the inner insulation. This ensures
that the Tester measures the leakage between the selected conductor and the
outer shield, but removes the leakage path between conductors.

Other manuals for Fluke 1550C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fluke 1550C and is the answer not in the manual?

Fluke 1550C Specifications

General IconGeneral
Display type-
Housing colorGrey, Yellow
Maximum voltage5000 V
AC voltage range250 - 5000 V
Operating altitude0 - 2000 m
Overload protectionYes
Storage temperature (T-T)-20 - 65 °C
Operating temperature (T-T)-20 - 50 °C
Operating relative humidity (H-H)0 - 80 %
International Protection (IP) codeIP40
Battery technologySealed Lead Acid (VRLA)
Number of batteries supported1
Weight and Dimensions IconWeight and Dimensions
Depth277 mm
Width269 mm
Height160 mm
Weight3700 g