EasyManua.ls Logo

Fluke 1652C - Memory Mode

Fluke 1652C
66 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical Installation Tester
Making Measurements
29
Potential fields of other earthing installations may influence
the measurement.
Equipment (motors, capacitors) connected downstream of
the RCD may cause considerable extension of the tripping
time.
Note
If the L and N terminals are reversed, the tester will auto-swap them
internally and continue testing. If the tester is configured for UK
operation, testing will halt and you will need to determine why the L
and N are swapped. This condition is indicated by arrows above or
below the terminal indicator symbol ().
Type A and type B RCDs do not have the 1000 mA option available.
To measure RCD tripping time:
1. Turn the rotary switch to the ΔT position.
2. Press to select the RCD current rating (10, 30, 100, 300, 500, or
1000 mA).
3. Press to select a test current multiplier (x ½, x 1, x 5, or Auto). Normally
you will use x 1 for this test.
4. Press to select the RCD test-current waveform:
– AC current to test type AC (standard AC RCD) and type A
(pulse-DC sensitive RCD)
– Half-wave current to test type A (pulse-DC sensitive RCD)
– Delayed response to test S-type AC (time delayed AC RCD)
– Delayed response to S-type A (time delayed pulse-DC
sensitive RCD)
– Smooth-DC current to test type B RCD
– Delayed response to S-type B (time delayed smooth-DC
current RCD)
5. Press to select the test current phase, 0° or 180°. RCDs should be
tested with both phase settings, as their response time can vary
significantly depending on the phase.
Note
For RCD type B () or S-type B ( ), you must test with both
phase settings.

Table of Contents

Other manuals for Fluke 1652C

Related product manuals