EasyManua.ls Logo

Fluke 1652C - Measuring RCD Tripping Current

Fluke 1652C
66 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1652C/1653B/1654B
Users Manual
32
Measuring RCD Tripping Current
apx009f.eps
Figure 17. RCD Tripping Current/Switch and Terminal Settings
This test measures the RCD tripping current by applying a test current and then
gradually increasing the current until the RCD trips. You can use the test leads
or mains cord for this test. A 3-wire connection is required.
 Warning
Test the connection between the N-conductor and earth
before starting the test. A voltage between the N-conductor
and earth may influence the test.
Leakage currents in the circuit following the residual current
protection device may influence measurements.
The displayed fault voltage relates to the rated residual
current of the RCD.
Potential fields of other earthing installations may influence
the measurement.
Note
If the L and N terminals are reversed, the tester will auto-swap them
internally and continue testing. If the tester is configured for UK
operation, testing will halt and you will need to determine why the L
and N are swapped. This condition is indicated by arrows above or
below the terminal indicator symbol ().
Type A and type B RCDs do not have the 1000 mA option available.
To measure RCD tripping current:
1. Turn the rotary switch to the I
ΔN
position.
2. Press to select the RCD current rating (10, 30, 100, 300, or 500 mA). If
the RCD has a special nominal current setting other than the standard

Table of Contents

Other manuals for Fluke 1652C

Related product manuals