EasyManua.ls Logo

Fluke PM6690 - Page 77

Fluke PM6690
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
the O N /O FF circuitry and the optional oven oscillator are
powered.
The AC/DC module should not be repaired. Not even the
built-in fuse should be replaced. Built-in circuits protect
against external overloads, so a blown fuse indicates that a se
-
vere internal fault has occurred. Replace the complete module
instead.
Test the AC/DC module by measuring the three DC voltages
inTP9(+5.1±0.05V),TP21(-15±1V)andTP26
(+15 ± 1 V) on the main circuit board. See Figure 6-55. Note
that there is a +5 V trimmer on the module. If the +5 V is not
correct, disconnect the cable to J17 on the main circuit board.
Put a 47 W 1 W resistor on the connector according to Figure
6-55. Measure on the connector +5.1 ± 0.05 V, +15 ± 1 V and
-15±1V.
It can be dif ficult to measure the resistance in the supply con
-
nector J17 on the main circuit board, because charges are kept
by capacitors some ti me after line power is removed. Remove
the cable from the AC/DC module. The resistance between
+5 V and ground should be approximatel y 700 W. See Figure
6-55. In a timer/counter with all capacitors uncharged, +15 V
and -15 V should be >1 MW.
Another way to test J17 is to connect 3 DC voltages from a
separate bench power supply directly to J17 (suitable connec
-
tor MOLEX 09-91-0600). See Figure 6-55. The currents
drawn from the different supply voltages depend on options
installed. Before making this measurement, you should re
-
move any prescaler option.
A timer/counter without options gives the following typical
results:
+5 V 0.7 A
+15 V 0.3 A
- 15 V 0.4 A
The oven oscillator increases the + 15 V current between
0.35 A (cold) and 0.1 A (warm).
A block diagram of the secondary power supply is shown in
Figure 6-54. All secondary voltages are switched off in
standby mode except +12 VU for the optional oven oscillator.
The ON/OFF circuitry controls the ON and OFF of the sec-
ondary voltages. Its own supply voltage is always ON, as long
as the instrument is connected to line power. See Figure 6-59.
Troubleshooting 6-33
X2
+1.8 V
U118
DC/DC
+3.3 VD
U128
DC/DC
+5 VD
U127
SWITCH
X14
X11
+3.3 VA
U126
LINEAR
X12
DUMMY
LOAD
Q56, Q57
ON/OFF
LOGIC
Q46, Q47,
Q58, U29
X22
X24
+12 VA
U129
LINEAR
+15 VD
Q49, Q50
SWITCH
X15
+12 VU
U130
LINEAR
X17
FAN
Q48, U30
+15 VU
+5 VU
J28
X16
mPROC.
X10
-12 VA
U123
LINEAR
-5.2 VA
U124
LINEAR
X8
X62
X25
-15 VU
J17:2,3
J17:1
J17:6
FROM AC/DC MODULE
+5 VA X13
mPROC.
KEY
-5.2 VI
Q51, U35
LINEAR
-2.1 V
Q17, U6
LINEAR
Figure 6-54 Power distribution
47 W
redbrown
b
rown
blackblackblue
AC/DC MODULE CABLE ASSEMBLY
PCB PIN CONNECTOR J17
X26
X9
X21
+15 V+5 V+5 VGNDGND-15 V
DUMMY LOAD
1
6
Figure 6-55 Dummy load connection.

Table of Contents

Other manuals for Fluke PM6690

Related product manuals