Figure 111 Service and maintenance schedules
Owner maintenance
(see FreeStyle
®
User’s Information
Manual)
Daily
y Check boiler area.
y Check air openings.
y Check pressure/temperature
gauge.
y Verify boiler jacket door is
securely in place.
Monthly
y Check vent piping.
y Check air piping.
y Check relief valve.
y Check condensate drain
system.
y Check automatic air vents
(if used).
y Verify that domestic hot
water is being supplied
to xtures at the correct
temperature.
Every
6 months
y Check boiler piping (gas and
water).
y Operate relief valve.
Part number 550-142-950/0122
85
FreeStyle
®
series
2
wall mount gas-fired water boiler – boiler manual
35 Annual startup and general maintenance
Follow the service and maintenance procedures given throughout this manual and in component literature shipped
with the boiler. Failure to perform the service and maintenance could result in damage to the boiler or system. Failure to
follow the directions in this manual and component literature could result in severe personal injury, death or substantial
property damage.
Service technician
(see page numbers indicated for details)
ANNUAL START-UP (See First-year special inspection)
y Handling ceramic ber materials . . . . . . . . . . . . . . . . . 86
y First-year special inspection . . . . . . . . . . . . . . . . . . . 86
y Address reported problems . . . . . . . . . . . . . . . . . . . 87
y Inspect boiler area . . . . . . . . . . . . . . . . . . . . . . . . 87
y Inspect boiler exterior . . . . . . . . . . . . . . . . . . . . . . 87
y Inspect boiler interior. . . . . . . . . . . . . . . . . . . . . . . 87
y Check all piping for leaks . . . . . . . . . . . . . . . . . . . . 87
y Check ignition wiring . . . . . . . . . . . . . . . . . . . . . . . 87
y Check all boiler wiring . . . . . . . . . . . . . . . . . . . . . . 87
y Check control settings . . . . . . . . . . . . . . . . . . . . . . 87
y Perform startup and checks . . . . . . . . . . . . . . . . . . . 87
y Check burner ame . . . . . . . . . . . . . . . . . . . . . . . 87
y Check boiler relief valve . . . . . . . . . . . . . . . . . . . . . 88
y Reinstall jacket door after servicing . . . . . . . . . . . . . . . 88
y Review with owner . . . . . . . . . . . . . . . . . . . . . . . . 88