Part number 550-142-950/0122
84
FreeStyle
®
series
2
wall mount gas-fired water boiler – boiler manual
34 Check-out/startup verication
Adjust and test boiler controls
1. Follow instructions in this manual to set and verify operation
of the boiler controls.
2. Follow low water cuto manufacturers instructions (if used).
Have the following been done?
Boiler and heat distribution units lled with water?
Water chemistry veried per page75?
Sentinel X100 corrosion inhibitor added and water tested to
be within range?
Air purged from system?
Air purged from gas piping? Piping checked for leaks?
Condensate trap primed?
If boiler has been converted to Liqueed Petroleum (LP) Gas
is propane conversion label axed to jacket?
FreeStyle® boilers are shipped ready to re natural
gas ONLY. To re on propane, you must follow the
instructions in this manual to install the propane
venturi. See page10 for FreeStyle® 80, 120 or 155.
Failure to comply could result in severe personal
injury, death or substantial property damage.
ermostat circuit wiring checked to ensure there are no
stray voltages?
Followed Operating Instructions, Figure105,page80?
Burner ame and combustion veried per page81?
FreeStyle® control operation for space heating and DHW (if
used) veried per this manual?
Additional eld-installed controls tested as outlined by con-
trol manufacturers? (Boiler should be operating and should go
o when controls are tested. Verify controls cause automatic
reset lockout or manual reset lockout as desired.)
Additional field-installed limit control(s) set to system
temperature requirements? Balancing valves and controls
adjusted to provide design temperature to system?
Flow adjusted/balanced for each zone of multiple zones
systems?
ermostat heat anticipator (if available) set properly?
Boiler cycled with thermostats (and with DHW aquastat, if
installed) — Raised to highest setting and veried boiler goes
through normal startup cycle? Lowered to lowest setting and
veried boiler goes o?
Natural gas input measured? (page81)
Incoming gas pressure checked by connecting manometer to
gas valve ahead of boiler? (Gas pressure must be at least the
minimum values given on page14, with boiler operating at
high re, and no more than 13 inches (330mm) w.c. with
boiler operating or boiler o.)
Observed several operating cycles for proper operation?
Room thermostats set to desired room temperature (and
DHW aquastat, if installed, to desired DHW storage tem-
perature)?
All instructions shipped with this boiler reviewed with owner
or maintenance person?
Ignition system safety shuto device tested?
Before leaving:
Fill in Installation certicate, page136.
Return instructions to envelope and give to owner.
Fill out start-up data on the In-
stallation and Service Certicate,
page136.