Figure 53 0IPINGLAYOUTTYPICALPIPINGFORMULTIPLEBOILERSBOILERSYSTEMSHOWNWITH$(7STORAGEHEATERSGROUPEDAS
ZONEINSECONDARYLOOPOFFPRIMARYSYSTEMLOOP(EATING/NLY
Part number 550-142-850/0716
46
FreeStyle
®
WALL MOUNT GAS-FIRED WATER BOILER — Boiler Manual
DHW tank piping with multiple
FreeStyle
®
boilers
DHW direct connection—single tank
1. )F"45(OUTPUTOFASINGLEBOILERISSUFlCIENTFORTHE
DHW tank/demand, pipe the indirect water heater to
the last boiler in the firing sequence. This will allow the
previous boilers to continue space heating while the last
boiler delivers DHW priority.
2. 0IPE FROMTHE NEARBOILERPIPING TOTHE $(7 TANKS
boiler connections as shown in Figure 48, page 41.
3. Connect the DHW tank aquastat directly to the DHW
input on the last boiler in the sequence.
When using a multiple-boiler control with lead boiler
rotation, it is recommended that the boiler connected to
the DHW tank is always set as the last boiler to operate
in the sequence so that space heat can be maintained
DURINGTIMESOF$(7DEMAND
DHW tanks as zone—multiple tanks
1. )FUSINGMULTIPLE$(7TANKSORMULTIPLEBANKSOFTANKSPIPETHE
tanks to the primary system loop with a secondary connection as
shown in Figure 53.
2. DHW tanks are zoned with circulators as shown.
3. )F$(7 PRIORITYIS REQUIREDUSE SEPARATE ZONECONTROLLERSFOR
DHW and space heating.
18
Multiple boiler installations
(continued)