QUANTUM™ COMPRESSOR CONTROL PANEL S90-010 M
MAINTENANCE Page 51
USER SELECTABLE CONTROL MODE #1
setting default range
Capacity Control Setpoint ______ 150°F 32 - 482°F
Upper Proportional Band ______ 4°F 0 - 20°F
Upper Dead Band ______ 1°F 0 - 10°F
Upper Cycle Time ______ 3 sec. 0 - 60 sec.
Lower Proportional Band ______ 4°F 0 - 20°F
Lower Dead Band ______ 1°F 0 - 10°F
Lower Cycle Time ______ 3 sec. 0 - 60 sec.
Autocycle Start Temp ______ 160°F 32 - 482°F
Autocycle Start Delay ______ 1 min. 0 - 60 min.
Autocycle Stop Temp ______ 140°F 32 - 482°F
Autocycle Stop Delay ______ 1 min. 0 - 60 min.
Low Suction Pressure Stop Load ______ 10 psig 30" - 135 psig
Low Suction Pressure Force Unload ______ 5 psig 30" - 135 psig
Low Suction Pressure Alarm ______ 2 psig 30" - 135 psig
Low Suction Pressure Alarm Delay ______ 3 sec. 0 - 60 sec.
Low Suction Pressure Shutdown ______ 0 psig 30" - 135 psig
Low Suction Pressure Shutdown Delay ______ 3 sec. 0 - 60 sec.
USER SELECTABLE CONTROL MODE #2
setting default range
Capacity Control Setpoint ______ 150°F 32 - 482°F
Upper Proportional Band ______ 4°F 0 - 20°F
Upper Dead Band ______ 1°F 0 - 10°F
Upper Cycle Time ______ 3 sec. 0 - 60 sec.
Lower Proportional Band ______ 4°F 0 - 20°F
Lower Dead Band ______ 1°F 0 - 10°F
Lower Cycle Time ______ 3 sec. 0 - 60 sec.
Autocycle Start Temp ______ 160°F 32 - 482°F
Autocycle Start Delay ______ 1 min. 0 - 60 min.
Autocycle Stop Temp ______ 140°F 32 - 482°F
Autocycle Stop Delay ______ 1 min. 0 - 60 min.
Low Suction Pressure Stop Load ______ 10 psig 30" - 135 psig
Low Suction Pressure Force Unload ______ 5 psig 30" - 135 psig
Low Suction Pressure Alarm ______ 2 psig 30" - 135 psig
Low Suction Pressure Alarm Delay ______ 3 sec. 0 - 60 sec.
Low Suction Pressure Shutdown ______ 0 psig 30" - 135 psig
Low Suction Pressure Shutdown Delay ______ 3 sec. 0 - 60 sec.