QUANTUM™ COMPRESSOR CONTROL PANEL S90-010 M
MAINTENANCE Page 43
Balance Piston Setup:
Enable Disable
Output on
slide valve %
default 70%
Output off
slide valve %
default 60%
Ignore Delay
(0 - 10) min.
default 5
Fail Delay
(0 - 10) min.
default 2
Oil Log Setup:
Enable Disable Fail Delay(15 - 120) sec. default 30
Main Oil Injection Safeties:
Enable Disable
Actual Setpoint (5.0 - 50.0 PSIG)
default 15
Fail Delay (0 - 60) sec.
default 30
Ram DBS Starter:
Enabled Disabled Using CT
PANEL SETUP
Pressure units:
Psia Psig BarA Bar Kpaa
Temperature units:
°F °C
Language:
English Danish German Spanish Other
Communications:
ID Number: _________ (range: 0 - 99)
Comm. 1 Baud rate:
1200 2400 4800 9600* 19200 38400 76800 115200
*Default
Comm. 2 Baud rate:
1200 2400 4800 9600* 19200 38400 76800 115200
*Default
Communication Protocols:
Frick
*
Allen Bradley Modbus York ISN
*Default