QUANTUM™ COMPRESSOR CONTROL PANEL S90-010 M
MAINTENANCE Page 53
OIL LEVEL DELAY
setting default range
Oil Level Delay ______ 300 sec. 0 - 600 sec.
MOTOR CONTROL
setting default range
Motor Amps ______ 100 0 - 3000
Volts ______ 480 0 - 5000
Service Factor ______ 1.15* 0.0 - 2.0
Horse Power ______ 100 0 - 3000
CT Factor ______ 100* 0 - 3000
Recycle Delay ______ 20 min. 20 - 255 min.
High Motor Amps Stop Load ______ 110 amps 0 - 3000 amps
High Motor Amps Force Unload ______ 115 amps 0 - 3000 amps
High Motor Amps Alarm ______ 120 amps 0 - 3000 amps
High Motor Amps Alarm Delay ______ 5 sec. 0 - 60 sec.
High Motor Amps Shutdown ______ 125 amps 0 - 3000 amps
High Motor Amps Shutdown Delay ______ 5 sec. 0 - 300 sec.
Low Motor Amps Shutdown ______ 25 amps 0 - 60 amps
Low Motor Amps Shutdown Delay ______ 30 sec. 0 - 60 sec.
Force Unload Inhibit Delay (If Applicable) ______ 120 sec. 10 - 300 sec.
*Blank if Ram DBS Starter
POWER FAILURE RESTART
Time after power failure allowing restart: ______ Hour ______ Minutes (Default 10 min.)