FRICK
®
QUANTUM™ COMPRESSOR CONTROL PANEL S90-010 CS (APR 08)
COMMUNICATIONS SETUP Page 19
RETURN Discharge Pressure Capacity Control
Mode 1 & 2 setpoints – Page 0: $01d0
$ Start of command sequence.
01 Compressor ID code.
D0 Discharge Pressure Capacity Control
Page 0 command
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character
Position
Description of returned data
1 A Acknowledge
2 01 Compressor ID code.
4 Discharge Pressure Control 1
13 Discharge Pressure Upper Prop. Band 1
22 Discharge Pressure Lower Prop. Band 1
31 Discharge Pressure Upper Dead Band 1
40 Discharge Pressure Lower Dead Band 1
49 Discharge Pressure Upper Cycle Time 1
58 Discharge Pressure Lower Cycle Time 1
67 Discharge Pressure Auto Start Setpoint 1
76 Discharge Pressure Auto Stop Setpoint 1
85 Discharge Pressure Auto Start Delay 1
94 Discharge Pressure Auto Stop Delay 1
103 CS (Checksum followed by Carriage
return, Line feed.)
RETURN Discharge Pressure Capacity Control
Mode 1 & 2 setpoints – Page 1: $01d1
$ Start of command sequence.
01 Compressor ID code.
D1 Discharge Press. Cap. Control Page 1
command
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character
Position
Description of returned data
1 A Acknowledge
2 01 Compressor ID code.
4 Discharge Pressure Control 2
13 Discharge Pressure Upper Prop. Band 2
22 Discharge Pressure Lower Prop. Band 2
31 Discharge Pressure Upper Dead Band 2
40 Discharge Pressure Lower Dead Band 2
49 Discharge Pressure Upper Cycle Time 2
58 Discharge Pressure Lower Cycle Time 2
67 Discharge Pressure Auto Start Setpoint 2
76 Discharge Pressure Auto Stop Setpoint 2
85 Discharge Pressure Auto Start delay 2
94 Discharge Pressure Auto Stop delay 2
103 CS (Checksum followed by Carriage
return, Line feed.)
RETURN Discharge Pressure Capacity Control
Mode 1 & 2 setpoints – Page 2: $01d2
$ Start of command sequence.
01 Compressor ID code.
D2 Discharge Pressure Capacity Control
Page 2 command
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character
Position
Description of returned data
1 A Acknowledge
2 01 Compressor ID code.
4 Discharge Pressure Stop Load 1
13 Discharge Pressure Force Unload 1
22 Discharge Pressure Low Alarm 1
31 Discharge Pressure Low Shutdown 1
40 Discharge Pressure Low Alarm delay 1
49 Discharge Pressure Low Shutdown delay 1
58 Discharge Pressure Stop Load 2
67 Discharge Pressure Force Unload 2
76 Discharge Pressure Low Alarm 2
85 Discharge Pressure Low Shutdown 2
94 Discharge Pressure Low Alarm delay 2
103 Discharge Pressure Low Shutdown delay 2
112 CS (Checksum followed by Carriage
return, Line feed.)
RETURN Discharge Pressure Capacity Control
Mode 1 & 2 setpoints – Page 3: $01d3
$ Start of command sequence.
01 Compressor ID code.
D3 Discharge Press. Cap. Control Page 3
command
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character
Position
Description of returned data
1 A Acknowledge
2 01 Compressor ID code.
4 User Selectable Control 1
13 User Selectable Upper Prop. Band 1
22 User Selectable Lower Prop. Band 1
31 User Selectable Upper Dead Band 1
40 User Selectable Lower Dead Band 1
49 User Selectable Upper Cycle Time 1
58 User Selectable Lower Cycle Time 1
67 User Selectable Auto Start Setpoint 1
76 User Selectable Auto Stop Setpoint 1
85 User Selectable Auto Start Delay 1
94 User Selectable Auto Stop Delay 1
103 CS (Checksum followed by Carriage return
Line feed.)