SPECIFICATIONS
Electrical Data
VRP
Model
Voltage Heater
Watts
Heating
Btu
Heater
Amps
ID Blower
Amps
OD
Blower
Amps
MCA MOP /
MOCP
VRP12K 230 2500 8530 11.2 0.34 0.42 14.0 15
208 2030 6980 10.2 0.38 0.42
230 3400 11601 15.1 0.34 0.42 18.9 20
208 2780 9480 13.8 0.38 0.42
230 5000 17060 22 0.34 0.42 27.5 30
208 4100 13980 20.1 0.38 0.42
VRP12R 265 2500 8530 9.8 0.2 0.4 12.3 15
3400 11601 13.2 0.2 0.4 16.5 20
5000 17060 19.3 0.2 0.4 24.1 25
MCA = Minimum Circuit Ampacity
MOP / MOCP = Maximum Overcurrent Protection / Breaker Size
Minimum Circuit Amps (MCA) and MOCP values in the above table are
calculated in accordance with The NEC. Article 440