107
EN-US
Field adjustable
trip points
Relevant stan-
dards and direc-
tives
Field adjustable trip points 208 V 240 V
Nominal AC output voltage,
Line-to-Line, [V]
208 240
Operating AC voltage range default,
Line-to-Line, [V]
183-229 212-264
Adjustment range for voltage,
Line-to-Line, [V]
180-240 180-270
Voltage trip limit accuracy
Line-to-Line,
[% of nominal value]
± 1,5 ± 1,5
Nominal output frequency [Hz] 60 60
Operating frequency range [Hz] 59.3-60.5 59.3-60.5
Adjustment range for frequency [Hz] 57.0-60.5 57.0-60.5
Frequency trip limit accuracy, [Hz] ± 0,02 ± 0,02
Reconnect time, [s] 305 305
Adjustment range for reconnect time, [s] 1-999 1-999
Operating AC voltage range
Line-to-Neutral, [V]
106 - 132 106 - 132
Adjustment range for voltage
Line-to-Neutral, [V]
60 - 144 60 - 144
Voltage trip limit accuracy
Line-to-Neutral,
[% of nominal value]
± 1,5 ± 1,5
- UL 1741
- IEEE 1547
- IEEE 1547.1
- ANSI/IEEE C62.41
- FCC Part 15 A & B
- NEC Article 690
- C22. 2 No. 107.1-01
(September 2001)