Choosing the Location
Choosing the lo-
cation in general
Please note the following criteria when choosing a location for the inverter:
It should only be installed on a stable, vertical wall.
Max. ambient temperatures: -20 °C / +55 °C
Relative humidity: 0 - 95 %
For use at altitudes above sea level: up to 2,000 m
- There should be a 200 mm clearance on both sides of the inverter for the cool air
vents.
- When installing more than one unit, keep a distance of 300 mm between individual
Fronius IG TL units.
The air flow direction within the inverter is from left to right (cold air intake on the left, hot
air outflow on the right).
When installing the inverter in a switch panel cabinet (or similar closed environment), it is
necessary to make sure that the hot air that develops will be discharged by forced ventila-
tion.
The inverter is designed for installation both indoors and outdoors.