EasyManua.ls Logo

Fronius IG-TL 4.0 - Criteria for the Proper Selection of String Fuses; General; Effects of Using Underrated Fuses; Fuse Recommendations

Fronius IG-TL 4.0
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42
Criteria for the Proper Selection of String Fuses
General The use of string fuses in the inverter also adds fuse protection to the solar modules.
A crucial factor for the fuse protection of solar modules is the maximum short circuit current
I
sc
of the respective solar module.
Criteria for the
Proper Selection
of String Fuses
The following criteria must be met for each solar module string when using fuse protection:
-I
N
> 1.5 x I
SC
-I
N
< 2.0 x I
SC
-U
N
850 V DC
- Fuse dimensions: Diameter 10.3 x 35 - 38 mm
Effects of Using
Underrated Fuses
With underrated fuses, the nominal current value may be less than the short circuit current
of the solar module.
Effect:
The fuse may trip in intensive lighting conditions.
Fuse recommen-
dations
You should only use the following fuses, which have been tested by Fronius, to ensure
problem-free fuse protection:
- Cooper Bussmann PV fuses
Fronius shall not be liable for any damage or other incidents resulting from the use of other
fuses. Moreover, all warranty claims are voided.
Application ex-
ample
Example: Maximum short circuit current (I
SC
) for the solar module = 5.75 A
According to the criteria for selecting the correct fuse, the fuse must have a nominal current
greater than 1.5 times the short circuit current:
5.75 A x 1.5 = 8.625 A
The fuse that should be selected according to the ‘Fuses’ table:
PV-10A10F with 10 A and nominal voltage of 1000 V DC.
I
N
Nominal current rating of the fuse
I
SC
Short circuit current for standard test conditions (STC) according to solar mod-
ule data sheet
V
N
Nominal voltage rating of the fuse
NOTE! Only select fuses suitable for a voltage of 850 V DC.

Table of Contents

Related product manuals